OGE Energy : OG&E - Rebuttal Testimony Robert Doupe

OGE

CASE PUD 2023-000087 ENTRY NO. 263 FILED IN OCC COURT CLERK'S OFFICE ON 05/17/2024 - PAGE 1 OF 7

BEFORE THE CORPORATION COMMISSION OF THE STATE OF OKLAHOMA

IN THE MATTER OF THE APPLICATION OF

)

OKLAHOMA GAS AND ELECTRIC COMPANY

)

FOR AN ORDER OF THE COMMISSION

)

AUTHORIZING APPLICANT TO MODIFY ITS

) CASE NO. PUD 2023-000087

RATES, CHARGES, AND TARIFFS FOR RETAIL

)

ELECTRIC SERVICE IN OKLAHOMA

)

Rebuttal Testimony

of

Robert Doupe

On behalf of

Oklahoma Gas and Electric Company

May 17, 2024

Rebuttal Testimony of Robert Doupe

Page 1 of 7

Case No. PUD 2023-000087

CASE PUD 2023-000087 ENTRY NO. 263 FILED IN OCC COURT CLERK'S OFFICE ON 05/17/2024 - PAGE 2 OF 7

Robert Doupe

Rebuttal Testimony

3

Oklahoma 73102.

4

5 Q. Are you the same Robert Doupe that filed Direct Testimony in this case on December

6

29, 2023?

7

A.

Yes.

8

13

operationally appropriate for the Company's wind assets and not 30 years as proposed by

14

Federal Executive Agencies' ("FEA") witness Brian Andrews, Public Utility Division

15

("PUD") witness William Dunkel and OIEC witness David Garrett.

16

17

COAL INVENTORY

18 Q. Please describe Mr. Norwood's recommendation regarding the Company's coal

19

inventory value and level.

20

A.

Mr. Norwood recommends a reduction for the total company coal inventory of

21

approximately $76 million. He believes that OG&E has an "excessive volume of

22

inventory," as a result of declining production from the Company's coal units. Instead of

23

OG&E basing its coal inventory levels off a full day's burn, Mr. Norwood proposes

24

calculating a lower coal inventory level of 962,406 tons using an average burn rate of

25

22,382 tons per day, which translates to a recommended coal inventory of 43 days.

Rebuttal Testimony of Robert Doupe

Page 2 of 7

Case No. PUD 2023-000087

CASE PUD 2023-000087 ENTRY NO. 263 FILED IN OCC COURT CLERK'S OFFICE ON 05/17/2024 - PAGE 3 OF 7

3

appropriate standard to use in calculating how many days of coal to maintain is the full day

4

burn rate. The entire purpose of having a coal inventory is to ensure the plant can operate

5

at full power during periods of supply disruptions. An inventory level based on an average

6

burn rate would not have enough coal to supply fuel during periods of high demand for a

7

long enough duration to provide security and reliability. Mr. Norwood's coal inventory

8

recommendation would only be approximately 34 days of coal at a full burn rate of

9

approximately 28,000 tons per day, which I believe is too low and would hinder the amount

10

of coal generation available to provide reliable power to our customers. OG&E's proposed

11

level of coal inventory is approximately 90 days of coal at a full day's burn rate. This coal

12

inventory level is appropriate given the coal supply disruptions in the recent past and the

13

need for greater coal inventory on the ground to preserve reliability.

14

17

coal burn is based on a faulty premise. The purpose of having coal inventory is not to

18

match historical average coal usage. The purpose of coal inventory is to ensure reliability

19

by having enough coal supply to handle disruptions in supply. The Company needs to

20

maintain a level of coal inventory that allows it to use the most economical and reliable

21

generation resources at any given time. In some months, this may require significantly

22

more coal usage than in others. Therefore, OG&E does not believe it is appropriate to set

23

coal inventory solely based on a simple average coal burn.

24

25 Q. Why is it appropriate to base coal inventory levels on a full burn instead of an average

26

day burn?

30

Operating Plan ("EOP") aimed at maintaining reliable power system operation in the

31

region and preventing widespread or major power outages due to insufficient generating

Rebuttal Testimony of Robert Doupe

Page 3 of 7

Case No. PUD 2023-000087

CASE PUD 2023-000087 ENTRY NO. 263 FILED IN OCC COURT CLERK'S OFFICE ON 05/17/2024 - PAGE 4 OF 7

1

capacity. The SPP EOP requires coal inventories to be reported in days at maximum output

2

for reliability purposes. Also, a full day burn rate is a constant number where an average

3

burn rate constantly changes due to outside variables. Looking at a historical number to

4

set future coal inventory levels could mean that we may not have an adequate amount of

5

coal to respond to a future event.

6

7 Q. Are there any other reasons why Mr. Norwood's 34-day coal inventory level is

8

inappropriate?

9

A.

Yes. Mr. Norwood's recommendation fails to take into account

the recent rail

10

transportation issues experienced by the Company that necessitated the Company's

11

increased inventory levels. In 2021 and 2022, OG&E experienced national rail

12

transportation delays of coal deliveries that led to rapidly declining coal inventory levels.

13

This caused OG&E to have to work with the SPP by developing market offering strategies

14

to limit off-peak coal generation in an effort to conserve coal for when needed most for

15

customers.1

16

The purpose of having coal inventory is not to match historical average coal usage,

17

but to ensure future reliability by having enough coal supply to manage disruptions in

18

supply. A larger coal inventory helps protect customers from future delivery disruptions.

19

Analyses using the average daily coal burn calculation also overlook the seasonality of

20

dispatch/utilization of OG&E's units in the Southwest Power Pool Integrated Market

21

("SPP IM"). The Company must maintain a higher inventory level to comply with SPP

22

dispatch requirements and to mitigate supply chain and rail transportation disruptions.

23

OG&E believes that a higher coal inventory equivalent with the 90-day supply included in

24

the requested rate increase is necessary for reliability going forward.

OG&E does not

25

believe it is appropriate to set coal inventory solely based on an average day coal burn and

26

previous coal inventory levels that do not take into account future risks to reliability and

27

the Company's customers.

1Direct Testimony of Shawn McBroom filed in Case No. PUD 2023-000055.

Rebuttal Testimony of Robert Doupe

Page 4 of 7

Case No. PUD 2023-000087

CASE PUD 2023-000087 ENTRY NO. 263 FILED IN OCC COURT CLERK'S OFFICE ON 05/17/2024 - PAGE 5 OF 7

1

WIND AND SOLAR ASSETS

2 Q. What are recommendations of FEA witness Brian Andrews, PUD witness William

3

Dunkel and OIEC witness David Garrett regarding the service life of the Company's

4

wind assets?

5

A.

All three witnesses propose a 30-year service life for the Company's wind assets. None of

6

the witnesses provide any evidence for their recommendations other than citing a survey

7

and erroneously pointing to OG&E's Integrated Resource Plan ("IRP").

8

11

their age and vintage. OG&E witness Riley explains why the survey used by the intervenor

12

witnesses actually supports a 25-year service life (and not a 30-year life) for OG&E's

13

specific wind assets. Also, she explains that OG&E's IRP uses a 30-year life for new wind

14

generation but has used a 25-year life consistently as an assumption for OG&E's existing

15

wind assets.

16

19

This is confirmed by the manufacturer design life certificates OG&E has received for the

20

wind turbines at OG&E's wind facilities. For example, the Crossroads wind turbines have

21

a manufacturer certificate from Siemens for a design life of 20 years. The Crossroads

22

turbines are the same Siemens turbines that have been installed at the OU Spirit wind farm.

23

It certainly makes sense to have a service life of 25 years as opposed to 30 years for turbines

24

with a design life certificate for 20 years. Also, the GE turbines used at the Centennial

25

facility should also have a 25-year life given their age and vintage. First constructed in

26

2006, they are the very first wind turbines installed in the OG&E generation portfolio. GE

27

promotional materials for these turbines shows that this vintage of turbines underwent 20-

28

year fatigue testing. I could find nothing from GE that would indicate anything longer than

29

25 years is advisable or recommended.

Rebuttal Testimony of Robert Doupe

Page 5 of 7

Case No. PUD 2023-000087

CASE PUD 2023-000087 ENTRY NO. 263 FILED IN OCC COURT CLERK'S OFFICE ON 05/17/2024 - PAGE 6 OF 7

3

2015 have used a 25-year life.

4

5 Q. Has the Commission specifically authorized the use of a 25-year service life for the

6

Company's wind farms?

7

A.

Yes. In the Company's 2015 rate case2 this Commission agreed with the Administrative

8

Law Judge ("ALJ") authorizing OG&E to utilize a 25-year life span for the Company's

9

wind farms.

10

11 Q. What was the ALJ's reasoning for recommending the Company utilize a 25-year

12

service life instead of 30?

13

A.

One of the reasons the ALJ recommended a 25-year service life was because "[w]hen the

14

Commission approved the OG&E units, the Commission based useful life on the

15

manufacturer's suggested useful life, which was then twenty-five years."3

16

The same reasoning in 2015 still applies in 2024. The Company's wind assets are

17

the same vintage, make, and model that were approved by the Commission when the units

18

were first placed into service. The Company's wind assets do not possess this newer

19

technology so there is no reason to change the current service life of 25 years to 30 years.

20

Furthermore, in 2015, the ALJ pointed out the proponents of a 30-year service life "lacked

21

an engineering study showing that at each OG&E owned wind farm, the model or models

22

of wind turbines used at that wind farm would be economic to operate for thirty years."4

23

As in 2015, no party in this current rate case has produced an engineering report or any

24

other evidence refuting the Company's 25 year service life for its wind assets.

25

28

It is not appropriate at this time to increase the life span of the assets to 30 years based on

2

3

4

Cause No. PUD 2015000273, Order No. 662059, at pg. 9.

Cause No. PUD 20150073, Report of the Administrative Law Judge at pg. 61. Id., pgs. 61-62.

Rebuttal Testimony of Robert Doupe

Page 6 of 7

Case No. PUD 2023-000087

CASE PUD 2023-000087 ENTRY NO. 263 FILED IN OCC COURT CLERK'S OFFICE ON 05/17/2024 - PAGE 7 OF 7

1

speculation by Mr. Norwood and Mr. Garrett that the Company wind assets might be able

2

to last longer.

3

9

technology is evolving rapidly. For example, the Covington solar farm constructed in 2017

10

are only mono-facial panels and rated at 250 Watts, but OG&E's Davis and Durant

11

facilities constructed in 2020 are 405 Watts with bi-Facial panels (which collect the sun's

12

irradiance from both sides of the panels). We are now seeing proposals for 550-watt panels.

13

These panels will require less area and provide the same power. It does not make sense to

14

push the cost recovery out for a period longer than 25 years when technology is developing

15

so rapidly, creating the potential for solar facilities to become obsolete and unsupported

16

before the end of their service life. I would recommend that we stay with the 25-year life

17

for our existing solar farm given this rapid technological evolution.

18

Second, given the frequency of severe weather in Oklahoma (including damaging

19

hailstorms), a longer service life is not advisable. I therefore disagree with the

20

recommendations by the PUD and OIEC to extend the service lives for solar to 30 years.

21

Rebuttal Testimony of Robert Doupe

Page 7 of 7

Case No. PUD 2023-000087

Disclaimer

OGE Energy Corporation published this content on 29 August 2024 and is solely responsible for the information contained therein. Distributed by Public, unedited and unaltered, on August 29, 2024 at 18:25:15 UTC.